今天带来变压器电抗标幺值怎么计算「电抗器的标幺值」,关于变压器电抗标幺值怎么计算「电抗器的标幺值」很多人还不知道,现在让我们一起来看看吧!
根据材料回答下题:
354、正序阻抗标幺值X1、X2、X3最接近下列哪项数值?(基准容量Sj=100MVA)( )
A、0.1612,-0.0056,0.0944
B、0.0806,-0.0028,0.0472
C、0.0806,-0.0028,0.0944
D、0.2611,-0.0091,0.1529
解答:根据《电力工程电气设计手册》电气一次部分、121页,表4-2和表4-4
等值电抗:
U1=1/2(UK(1-2) UK(1-3)-UK(2-3))=1/2(14 23-8)=14.5
U2=1/2(UK(1-2) UK(2-3)-UK(1-3))=1/2(14 8-23)=-0.5
U3=1/2(UK(1-3) UK(2-3)-UK(1-2))=1/2(23 8-14)=8.5
电抗标幺值:
X1=(U1%/100)*(Sj/Se)=(14.5/100)*(100/180)=0.0806
X2=(U2%/100)*(Sj/Se)=(-0.5/100)*(100/180)=0.0028
X3=(U3%/100)*(Sj/Se)=(8.5/100)*(100/180)=0.0472
本题正确选项是B